Fuel Consumption
See Figure 7 for fuel supply requirements at half and full
load for both natural gas and LP vapor.
_,K_ Iv_ lalP-ll_!lcJ_'j___
Model Natural Gas* LP Vapor **
I/2 Full I/2 Load Full Load
Load Load
1931-0 84 162 34.19 65.8 I
* = Natural Gas is in cubic feet per hour
** = LPVapor isin cubic feet per hour
Fuel Pipe Sizing
Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.
Listed values compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, please refer
to federal and local codes.
I Oft
Y2" 168
¾" 346
I" 653
Natural Gas (sg=0.65)
15E 50E
146 115 93 79 70
293 240 192 163 145
549 446 360 307 274
60_
63 59 55
132 120 113
250 230 211
90_ 100_
51 48
106 99
197 187
NPT 10_ 15_
½" II0 96
¾" 277 192
I" 428 360
Liquefied Petroleum (LP)(sg=l.50)
20_ 30_ 40_ 50_ 60_ 70_ 80_ 90_ 100k
76 61 52 46 42 38 36 33 32
158 126 107 95 87 79 74 69 65
293 236 202 180 164 151 139 129 123