Briggs & Stratton 1679-0 Installation Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
C_ byEe_'sCu__et
Bri_s & Stratton Power Products Home Generator System
Installation Manual
Fuel Comparison Chart
It'_l lit "_'mpm+l+t-,_+ [€ rRl_l
Physical Properties
Normal Atmospheric State
Boiling Point (in OF):
Initial
End
Butane
Gas
Propane
Gas
Natural Gas
Gas
32 +44 +259
32 -44 +259
Heating Value:
BTU per gallon (Net LHV*) 94,670 83,340 63,310
BTU per Gallon (Gross**) 102,032 91,547
Cubic Feet (Gas) 3,264 2,516 1,000
Density*** 31.26 36.39 57.75
Weight-_ 4.81 4.24 2.65
Octane Number:
Research 94 110+ 110+
Motor 90 97
LHV (Low HeatValue) is the more realistic rating.
** Gross HeatValue does not consider heat lost in the form of water during combustion.
*** Density is given in "Cubic Feet of Gas per Gallon of Liquid".
t Weight isgiven in "Pounds per Gallon of Liquid".
Size of Propane Tank Required at Various Temperatures When Kept at Least
Half Full
Given the gaswithdrawal rate and the lowestaveragewinter temperature, an installercan specifythe required LP storage
tank size:
Withdraw_ Rate 32°F 20°F 10°F 0°F -10°F -30°F -40°F
50 CFH 115 115 115 250 250 400 600
100CFH 250 250 250 400 500 1000 1500
150CFH 300 400 500 500 1000 1500 2500
200 CFH 400 500 750 1000 1200 2000 2500
300 CFH 750 1000 1500 2000 2500 4000 5000
I